蒸發冷卻模組應用於分離式空調機之開發與性能研究

dc.contributor鄧敦平zh_TW
dc.contributorTeng,Tun-Pingen_US
dc.contributor.author謝其霖zh_TW
dc.contributor.authorXie,Qi-Linen_US
dc.date.accessioned2020-10-19T06:49:51Z
dc.date.available2025-12-31
dc.date.available2020-10-19T06:49:51Z
dc.date.issued2020
dc.description.abstract本研究的蒸發冷卻模組是由水流分配系統搭配7條長柱狀紙纖維冷卻板組成。利用三種不同厚度的蒸發冷卻模組(CM1-CM3)分別裝置於分離式空調機的冷凝器進風口處。藉由水流分配系統將冷凝水均勻分配至冷卻板上,以間接蒸發冷卻的方式對進入冷凝器的空氣進行預冷,達到提升冷凝器的散熱性能與空調機的運轉效率。空調機性能試驗的環境條件則是參考CNS15712的低溫冷氣能力標準(C1)、CNS14464的T1標準(C2)及本研究自行增設的高溫條件(C3)。研究結果顯示,當實驗環境條件由C1上升到C2時,裝設蒸發冷卻模組的空調機的性能明顯提升。在C2實驗環境條件下是以裝設CM3的空調機能獲得最高的能源效率比(EER)及性能係數(COP),分別比原機提升4.30%、4.00 %。然而,在C3實驗環境條件下,裝設蒸發冷卻模組的空調機性能表現明顯下降。這種現象主要是因為高溫實驗環境條件導致空調機性能降低使得冷凝水量減少進而造成蒸發冷卻模組無法針對冷凝器進行有效蒸發冷卻所致。zh_TW
dc.description.abstractThe evaporative cooling module in this study is composed of a water flow distribution system and seven long cylindrical paper fiber cooling pads. Three types of evaporative cooling modules (CM1-CM3) with different thicknesses are respectively tested by being installed at the air inlet of the condenser of the separate air conditioner. Through the water flow distribution system, the condensate is evenly distributed to the cooling pad, and the air entering the condenser is pre-cooled by indirectly evaporative cooling to improve the heat dissipation performance of the condenser and the operating efficiency of the air conditioner. The environmental conditions of the air conditioner performance test refer to the low-temperature air-conditioning capacity test standard of CNS15712 (C1), the T1 test standard of CNS14464 (C2), and the high-temperature condition configured in the study (C3). The research results show that the performance of the air conditioner equipped with an evaporative cooling module is significantly improved when the experimental environmental conditions change from C1 into C2. The highest energy efficiency ratio (EER) and coefficient of performance (COP) were obtained with the air-conditioner equipped with CM3 under the experimental environmental conditions of C2, which is 4.30% and 4.00% higher than the original machine, respectively. However, the performance of the air conditioner with the evaporative cooling module was significantly reduced under the environmental conditions of C3. This phenomenon is mainly due to the fact that the high-temperature experimental environmental conditions lead to a decrease in the performance of the air conditioner such that the amount of condensed water reduces, and thus the evaporative cooling module cannot effectively pre-cool the condenser.en_US
dc.description.sponsorship工業教育學系zh_TW
dc.identifierG060770009H
dc.identifier.urihttp://etds.lib.ntnu.edu.tw/cgi-bin/gs32/gsweb.cgi?o=dstdcdr&s=id=%22G060770009H%22.&%22.id.&
dc.identifier.urihttp://rportal.lib.ntnu.edu.tw:80/handle/20.500.12235/111036
dc.language中文
dc.subject紙纖維冷卻板zh_TW
dc.subject間接式蒸發冷卻zh_TW
dc.subject空氣預冷zh_TW
dc.subject分離式空調機zh_TW
dc.subject能源效率比zh_TW
dc.subjectcooling padsen_US
dc.subjectindirect evaporative coolingen_US
dc.subjectair pre-coolingen_US
dc.subjectsplit type air conditioneren_US
dc.subjectenergy efficiency ratioen_US
dc.title蒸發冷卻模組應用於分離式空調機之開發與性能研究zh_TW
dc.titleDevelopment and Performance on Evaporative Cooling Unit applied to Split Type Air Conditioneren_US

Files